Additional information
| Temperature Adjustment Range | 38 to 50C |
|---|---|
| Dynamic Inlet Pressures | 20kPa Min – 500kPa Max |
| Static Inlet Pressure | 1600kPa Max |
| Flow Rates | 39lpm@300kPa pressure loss |
| Minimum Flow Rate for stable outlet temperature | 4 litres/min (4lpm is recommended for optimum performance) |
| Inlet size | 1/2" compression nuts |
| Outlet size | 1" complete with 1"x1/2" & 1"x 3/4" BSP adaptors |
| Inlet Temperatures | Cold Supply: Min 5 C Max 30 C Hot Supply: Min 55 C Max 90 C |